The leader in industrial automation and control solutions
Product comparison — attributes in rows, products in columns.

Filters

IO-SA0400

Analog RTD Module

IO-SA0400

$290
View Product
IO-SA0400T

Analog TC Module

IO-SA0400T

$315
View Product

View Product
IO-SA0400 IO-SA0400T N/A
Type RTD Thermocouple
Temperature Input Range PT100: -200.0–600°C; JPT100: -200.0–600°C; PT1000: -200.0– 600°C; Ni1000 (DIN 43760): -50.0–160°C; Ni1000 (TCR 5000): -50.0–160°C K: -200.0 – 1200.0°C; J: -200.0 – 800.0°C; E: -200.0 – 600.0°C; T: -200.0 – 400.0°C; B: 400.0 – 1800.0°C; R: 0.0 – 1750.0°C; S: 0.0 – 1750.0°C; N: -200.0 – 1250.0°C
Wire Disconnection Detection 3 wires per channel Each channel
Number of Input Channels 4 4
Max Conversion Rate 40 ms/4 Channels 50 ms/4 Channels
Insulation Type Photocoupler between input terminal and PLC power Photocoupler between input terminal and PLC power
Accuracy ±0.1% (full scale) ±[(Full Scale) x 0.3% + 1°C (RJC Error)]
IO-SA0400 IO-SA0400T N/A
Current Consumption +3.3V 40 mA 40 mA
Current Consumption +24V 10 mA 10 mA
IO-SA0400 IO-SA0400T N/A
Dimensions WxHxD 90 x 20 x 60 mm (3.5 x 0.8 x 2.4 in) 90 x 20 x 60 mm (3.5 x 0.8 x 2.4 in)
Weight 153 g (0.34 lb) 87 g (0.19 lb)
Shock 15G 15G
Vibration 0.5G – Continuous, 1G – Discontinuous 0.5G – Continuous, 1G – Discontinuous
Square Wave Impulse Noise ±2 kV ±2 kV
ESD Immunity ±4 kV – Contact Discharges, ±8 kV – Air Discharges ±4 kV – Contact Discharges, ±8 kV – Air Discharges
Radiated Electromagnetic Immunity 80–1000 MHz, 10 V/m 80–1000 MHz, 10 V/m
Surge Transient Immunity 2 kV – CPU, Power; 2 kV – Digital I/O (VAC); 1 kV – Digital I/O (VDC); 1 kV – Communication 2 kV – CPU, Power; 2 kV – Digital I/O (VAC); 1 kV – Digital I/O (VDC); 1 kV – Communication
IO-SA0400 IO-SA0400T N/A
Operating Temperature 10 – 65 °C (14 – 149 °F) 10 – 65 °C (14 – 149 °F)
Storage Temperature 25 – 80 °C (-13 – 176 °F) 25 – 80 °C (-13 – 176 °F)
Operating/Storage Relative Humidity 5 – 95% Non-condensing 5 – 95% Non-condensing
IO-SA0400 IO-SA0400T N/A
CE Yes Yes
UL Yes Yes