The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Siemens TI505 (Ethernet). Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: SIMATIC TI505 Series PLCs: TI520, TI525, TI530, TI535, TI545, TI555, TI560, TI565, TI575 with Ethernet

Websites: Siemens, CTI

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeSiemens TI505 (Ethernet)
PLC I/FEthernet
Port no.1505
PLC sta. no.1

Device Addresses

Bit/WordDevice TypeFormatRangeDescription
BCRDDDDD1 ~ 65536Internal Relay
BXDDDDD1 ~ 65536Discrete Input Coils
BYDDDDD1 ~ 65536Discrete Output Coils
BV_BitDDDDDdd101 ~ 6553616User Data Register Bits
WVDDDDD1 ~ 65536User Data Registers
DWVDDDDDD1 ~ 65535User Data Registers (32bit)
WSTWDDDDD1 ~ 65536Status Word Registers
WTCPDDDDD1 ~ 65536Timer/Counter Preset Values
WTCCDDDDD1 ~ 65536Timer/Counter Current
WWXDDDDD1 ~ 65536Word Discrete Inputs
WWYDDDDD1 ~ 65536Word Discrete Outputs

Wiring Diagram

NOTE: Connect the HMI to the PLC using a standard Ethernet cable (Cat5e or higher).

The diagram below shows the Ethernet cable wiring.

Standard Ethernet cable wiring diagram showing 8 color-coded wire pairs: W/Orange, Orange, W/Green, Blue, W/Blue, Green, W/Brown, Brown mapped to pins 1 through 8.