All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with LS Electric XGK FEnet Ethernet. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module

Website: http://www.lgis.com/

HMI Setting

ParametersRecommendedOptionsNotes
PLC typeLS XGK FEnet (Ethernet)
PLC I/FEthernet
Port no.2004

Device Address

Bit/WordDevice typeFormatRangeMemo
BPW_BitDDDDh0 ~ 4095fI/O device Bit
BMW_BitDDDDh0 ~ 4095fInternal device Bit
BLW_BitDDDDDh0 ~ 11263fCommunication device Bit
BKW_BitDDDDh0 ~ 4095fPreservation device Bit
BFW_BitDDDDh0 ~ 4095fSpecial device Bit (write available from 1025)
BSW_BitDDDDDh0 ~ 25599Relay for step control Bit
BDW_BitDDDDDh0 ~ 524287fData register — Bit expression (D0000.0)
BUW_BitDH.DDh0 ~ 7f.31fAnalog data register. XGK-CPUE: hh(0~1f)
BRW_BitDDDDDh0 ~ 32767f
BZRW_BitDDDDDDh0 ~ 524287f
BNW_BitDDDDDh0 ~ 21053f
BZW_BitDDDh0 ~ 255f
BTXDDDD0 ~ 8191Timer device Bit
BCXDDDD0 ~ 4095Counter device Bit
WPWDDDD0 ~ 4095I/O device
WMWDDDD0 ~ 4095Internal device
WLWDDDDD0 ~ 11263Communication device
WKWDDDD0 ~ 4095Preservation device
WFWDDDD0 ~ 4095Special device (write available from 1025)
WSWDDDDD0 ~ 255Relay for step control
WDWDDDDD0 ~ 524287Data register
WUWDH.DD0.00 ~ 7f.31Analog data register. XGK-CPUE: hh(0~1f)
WNWDDDDD0 ~ 21503Communication data register
WZWDDD0 ~ 255Index register — 128 words
WTWDDDD0 ~ 8191Timer current value register
WCWDDDD0 ~ 4095Counter current value register
WRWDDDDD0 ~ 32767
WZRWDDDDDD0 ~ 524287

Wiring Diagram

The diagram below shows the Ethernet cable wiring.

Straight-through Ethernet cable wiring diagram showing color-coded pairs: W/Orange, Orange, W/Green, Blue, W/Blue, Green, W/Brown, Brown on both ends.