The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with LS Electric XGI Fenet (Ethernet). Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: LS XGT series XGI CPU with XGL-EFMT 1thernet module

Protocol: LS XGI Fenet (Ethernet) — LS XGT series XGI CPU with XGL-EFMT Ethernet module

Website: http://www.lgis.com/

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeLS XGI Fenet (Ethernet)
PLC I/FEthernet
Port no.2004
PLC sta. no.0

Device Address

Bit/WordDevice TypeFormatRangeMemo
BAW_BitDDDDDDh0 ~ 262143f
BIW_BitDDD.DD.Dh0 ~ 127.15.3f
BQW_BitDDD.DD.Dh0 ~ 127.15.3f
BMW_BitDDDDDDDh0 ~ 1048575f
BRW_BitDDDDDh0 ~ 32767f
BWW_BitDDDDDDh0 ~ 524287f
BFW_BitDDDDh0 ~ 9125f
BKW_BitDDDDDh0 ~ 65535f
BLW_BitDDDDDh0 ~ 11263f
BNW_BitDDDDDh0 ~ 25087f
BUW_BitDD.DD.DDh0 ~ 31.15.31f
BAXDDDDDDD0 ~ 4194303
BIXDDD.DD.DD0 ~ 127.15.63
BQXDDD.DD.DD0 ~ 127.15.63
BMXDDDDDDD0 ~ 16777199
BRXDDDDDD0 ~ 524287
BWXDDDDDDD0 ~ 8388607
BFXDDDDDD0 ~ 146015
BKXDDDDDDD0 ~ 1048575
BLXDDDDDDD0 ~ 1880223
BNXDDDDDD0 ~ 401407
BUXDD.DD.DDD0 ~ 31.15.511
WAWDDDDDD0 ~ 262143
WIWDDD.DD.D0 ~ 127.15.3
WQWDDD.DD.D0 ~ 127.15.3
WMWDDDDDDD0 ~ 1048575
WRWDDDDD0 ~ 32767
WWWDDDDDD0 ~ 524287
WFWDDDDD0 ~ 65535
WKWDDDD0 ~ 9125
WLWDDDDD0 ~ 11263
WNWDDDDD0 ~ 25087
WUWDD.DD.DD0 ~ 31.15.31
DWMDDDDDDD0 ~ 524288
ByteMBDDDDDDD0 ~ 2097151
LWMLDDDDDD0 ~ 262143

Wiring Diagram

NOTE: Ethernet cable — use a standard straight-through Cat5e or Cat6 Ethernet cable to connect the HMI to the LS XGT PLC Ethernet module.

The diagram below shows the Ethernet cable wiring.

Straight-through Ethernet cable wiring diagram showing all eight twisted pairs color-coded: W/Orange, Orange, W/Green, Blue, W/Blue, Green, W/Brown, and Brown, with pin numbers 1–8 on both ends.