Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with LS Electric XBM/XBC Cnet. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: LS XGB Series XBM/XBC CPU with communication module

Website: http://www.lgis.com/

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeLS XBM/XBC Cnet
PLC I/FRS232RS232/RS485
Baud rate1152009600~115200
Data bits87, 8
ParityNoneEven, Odd, None
Stop bits11
PLC sta. no.10-31

Device Address

Bit/WordDevice typeFormatRangeMemo
BPW_BitDDDDh0 ~ 2047fI/O device Bit
BMW_BitDDDDh0 ~ 2047fInternal device Bit
BLW_BitDDDDDh0 ~ 11263fCommunication device Bit
BKW_BitDDDDh0 ~ 8191fPreservation device Bit
BFW_BitDDDDh0 ~ 2047fSpecial device Bit (write available from 1025)
BDW_BitDDDDDh0 ~ 32767fData register Bit expression (D0000.0)
BUW_BitDH.DDh0 ~ 7f.31fXGK-CPUE: hh(0~1f)
BRW_BitDDDDDh0 ~ 32767f
BSXDDDDD0 ~ 12799Relay for step control Bit
BTXDDDD0 ~ 2047Timer device Bit
BCXDDDD0 ~ 2047Counter device Bit
WPWDDDD0 ~ 2047I/O device — 2,048 points
WMWDDDD0 ~ 2047Internal device — 4,096 points
WLWDDDDD0 ~ 11263Communication device — 20,480 points
WKWDDDD0 ~ 8191Preservation device — 4,096 points
WFWDDDD0 ~ 2047Special device — 4,096 points
WDWDDDDD0 ~ 32767Data register — 5,120 words
WUWDH.DD0.00 ~ 7f.31Analog data register — 256 words
WRWDDDDD0 ~ 32767
WZRWDDDDDD0 ~ 262143
WSWDDDDD0 ~ 127Relay for step control
WTWDDDD0 ~ 2047Timer current value register — 256 words
WCWDDDD0 ~ 2047Counter current value register — 256 words
WNWDDDDD0 ~ 21503Communication data register — 3,936 words
WZWDDD0 ~ 127Index register — 128 words

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-232

HMIDirectionPLC
Pin assignmentsRS232
9P D-Sub
Male
Rx↔ (bidirectional)3
Tx↔ (bidirectional)2
GND↔ (bidirectional)5

Diagram 2: RS-485 2W

HMIDirectionPLC
Pin assignmentsRS485 2W
Terminal
Data-↔ (bidirectional)485-
Data+↔ (bidirectional)485+