Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with a Koyo (Automation Direct) CLICK V3 Modbus TCP/IP PLC. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: KOYO CLICK C0, C2 series

Website: automationdirect.com

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeKOYO CLICK V3 MODBUS TCP/IP
PLC I/FEthernet
Port no.502

Device Address

Bit/WordDevice typeFormatRangeMemo
BXDdd1 ~ 816
BYDdd1 ~ 816
BCDDDD1 ~ 2000
BTDDD1 ~ 500
BCTDDD1 ~ 250
BSCDDDD1 ~ 1000
BX0DD21 ~ 36X021-X036
BY0DD21 ~ 36Y021-Y036
BX1DD21 ~ 36X121-X136
BY1DD21 ~ 36Y121-Y136
BX2DD21 ~ 36X221-X236
BY2DD21 ~ 36Y221-Y236
BX3DD21 ~ 36X321-X336
BY3DD21 ~ 36Y321-Y336
BX4DD21 ~ 36X421-X436
BY4DD21 ~ 36Y421-Y436
BX5DD21 ~ 36X521-X536
BY5DD21 ~ 36Y521-Y536
BX6DD21 ~ 36X621-X636
BY6DD21 ~ 36Y621-Y636
BX7DD21 ~ 36X721-X736
BY7DD21 ~ 36Y721-Y736
BX8DD21 ~ 36X821-X836
BY8DD21 ~ 36Y821-Y836
WDSDDDD1 ~ 4500
DWDDDDDD1 ~ 1000
WDHDDD1 ~ 500
DWDFDDD1 ~ 500
WXDD0 ~ 8
WYDD0 ~ 8
WTDDDD1 ~ 500
DWCTDDDD1 ~ 250
WSDDDDD1 ~ 1000
WTXTDDDD1 ~ 1000
WXDuD0 ~ 8
WYDuD0 ~ 8

Wiring Diagram

The diagram below shows the Ethernet cable wiring.

Ethernet straight-through cable wiring diagram showing eight color-coded pairs: W/Orange, Orange, W/Green, Blue, W/Blue, Green, W/Brown, Brown — identical on both ends.