The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with GE Intelligent Platforms 90-30 Series (Ethernet). Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: GE 90-30 series, CPU model 374plus

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeGE 90-30 Series (Ethernet)
PLC I/FEthernet
Port no.18245
PLC sta. no.11~99

Device Address

Bit/WordDevice TypeFormatRangeMemo
BI_BitDDDDD1 ~ 32768
BQ_BitDDDDD1 ~ 32768
BM_BitDDDDD1 ~ 32768
BG_BitDDDDD1 ~ 32768
BT_BitDDDDD1 ~ 32768
BSA_BitDDDDD1 ~ 32768Read Only
BSB_BitDDDDD1 ~ 32768Read Only
BSC_BitDDDDD1 ~ 32768Read Only
BS_BitDDDDD1 ~ 32768Read Only
BR_BitDDDDDdd100 ~ 3276815
BW_BitDDDDDDDdd100 ~ 500000015
WIDDDDD1 ~ 32753Address increment by 8 words, ex: I1, I9, I17, I25…
WQDDDDD1 ~ 32753The rule is same as above, ex: Q1, Q9, Q17…
WMDDDDD1 ~ 32753The rule is same as above, ex: M1, M9, M17…
WGDDDDD1 ~ 32768The rule is same as above, ex: G1, G9, G17…
WTDDDD1 ~ 1024The rule is same as above, ex: T1, T9, T17…
WSADDDDD1 ~ 32753Read only, the rule is same as above
WSBDDDDD1 ~ 32753Read only, the rule is same as above
WSCDDDDD1 ~ 32768Read only, the rule is same as above
WSDDDDD1 ~ 32753Read only, the rule is same as above
WRDDDDD1 ~ 32768
WAIDDDDD1 ~ 32768
WAQDDDDD1 ~ 32768
WWDDDDDDD1 ~ 5000000

Wiring Diagram

NOTE: Connect the HMI to the GE 90-30 Series PLC using a standard Ethernet cable.

The diagram below shows the Ethernet cable wiring.

Ethernet cable wiring diagram showing T568B color-coded pairs: W/Orange, Orange, W/Green, Blue, W/Blue, Green, W/Brown, Brown on both ends.