The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with an Emerson Charge Module. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

HMI Setting

ParametersRecommendedOptionsNotes
PLC typeEMERSON Charge Module
PLC I/FRS-232
Baud rate9600
Data bits8
ParityOdd
Stop bits1
PLC sta. no.1

Device Address

Bit/WordDevice typeFormatRangeMemo
BFloat_Point_ForcedD0 ~ 1
BAverage_Point_ForcedD0 ~ 1
WSwitch_StatusD0 ~ 1
WManual_StatusD0 ~ 1
WProtect_StatusD0 ~ 1
WFailure_StatusD0 ~ 1
WPreset_VoltageD0 ~ 1
WPreset_PercentD0 ~ 1
WOutput_VoltageD0 ~ 1
WOutput_CurrentD0 ~ 1
WHigh_LimitD0 ~ 1
WLow_LimitD0 ~ 1
WFloat_Point_SettingD0 ~ 1
WAverage_Point_SettingD0 ~ 1

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-232

HMIDirectionPLC
Pin assignmentsRS232 Terminal
Rx↔ (bidirectional)TX
Tx↔ (bidirectional)RX
GND↔ (bidirectional)GND