The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Trio MODBUS RTU, TCP/IP (Mode 7). Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeTrio MODBUS RTU, TCP/IP (Mode 7)
PLC I/FRS485RS232/RS485/Ethernet
Baud rate96009600~115200
Data bits87, 8
ParityEvenEven, Odd, None
Stop bits11, 2
Port no.502
PLC sta. no.10–255
Online simulatorYES
Broadcast commandYES
Extend address modeYES

PLC Settings

ParameterValue
Communication modeModbus RTU protocol
PLC mode7 (IEEE floating point)

Device Address

Bit/WordDevice TypeFormatRangeMemo
BVR_BitDDDDDdd0 ~ 1638431
BVR_INT_BitDDDDDdd0 ~ 1638431
BTable_BitDDDDDdd0 ~ 3199931
BTable_INT_BitDDDDDdd0 ~ 3199931
WVRDDDDD0 ~ 16384
WVR_INTDDDDD0 ~ 16384
WTableDDDDD0 ~ 31999
WTable_INTDDDDD0 ~ 31999

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-232

HMIDirectionPLC
Pin assignmentsRS232
9P D-Sub
Male
Rx↔ (bidirectional)TXD
Tx↔ (bidirectional)RXD
GND↔ (bidirectional)GND
↕︎ (tie)RTS
CTS

Diagram 2: RS-485 2W

HMIDirectionPLC
Pin assignmentsRS485 2W
9P D-Sub
Male
Data-↔ (bidirectional)D-
Data+↔ (bidirectional)D+
GND↔ (bidirectional)GND

Diagram 3: RS-485 4W

HMIDirectionPLC
Pin assignmentsRS485 4W
9P D-Sub
Male
Rx-↔ (bidirectional)TX-
RX+↔ (bidirectional)TX+
Tx-↔ (bidirectional)RX-
Tx+↔ (bidirectional)RX+
GND↔ (bidirectional)GND

Diagram 4: Ethernet Cable