The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Toptek Topvert. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: TOPVERT G1/H1/P1 series

Website: http://www.toptek.biz/

HMI Setting

ParametersRecommendedOptionsNotes
PLC typeToptek Topvert
PLC I/FRS485 2W
Baud rate9600
Data bits7
ParityNone
Stop bits2
PLC sta. no.1
Online simulatorYES
Broadcast commandYES
Extend address modeYES
Broadcast station no.0

PLC Setting

ParameterValue
Communication modePr 7-15 = 0 (7, N, 2 ASCII)

Device Address

Bit/WordDevice typeFormatRangeMemo
BPR_BitDDDDDdd0 ~ 6553515G=Groups, F=Function no.
dd=0~15 bit no.
WPRDDDDD0 ~ 65535G=Groups, F=Function no.

Notes

Max. read-command size (words): 16

Max. write-command size (words): 1

For G1/H1/P1 Series Inverter, if standard parameter address is in decimal = 100*G+F:

G=Group (parameter group code 0~9); F=Function no. (parameter number 0~99)

For example: Pr5-20 (decimal) parameter address is expressed as 100*5+20=520.

Parameter Address Examples

Parameter (PrX-XX)Address (decimal)
0-000*100+0=0
0-140*100+14=14
1-001*100+0=100

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-485 2W

HMIDirectionPLC
Pin assignmentsRS485 2W
Terminal
Data-↔ (bidirectional)SG-
Data+↔ (bidirectional)SG+
GND↔ (bidirectional)GND