Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Schleicher XCS 20C. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: Schleicher XCx-Systems Ethernet port. Schleicher XCS series, 20C model
Website: www.schleicher-electronic.com
HMI Settings
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | Schleicher XCS 20C | ||
| PLC I/F | RS232 | ||
| Baud rate | 38400 | ||
| Data bits | 8 | ||
| Parity | N | ||
| Stop bits | 1 | ||
| PLC sta. no. | 0 |
Device Address
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| B | IX | DDDDDo | 0 ~ 655357 | Input %IX |
| B | QX | DDDDDo | 0 ~ 655357 | Output %QX |
| B | MX | DDDDDo | 0 ~ 655357 | %MX |
| W | IW | DDDDD | 0 ~ 65535 | %IW |
| W | QW | DDDDD | 0 ~ 65535 | %QW |
| W | MW | DDDDD | 0 ~ 65535 | %MW |
| DW | ID | DDDDD | 0 ~ 65535 | %ID |
| DW | QD | DDDDD | 0 ~ 65535 | %QD |
| DW | MD | DDDDD | 0 ~ 65535 | %WD |
NOTE: Word address must be even.
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.

RS-232
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | Schleicher XCS20 RS232 9P D-Sub Male | |
| Rx | ↔ (bidirectional) | 3 |
| Tx | ↔ (bidirectional) | 2 |
| GND | ↔ (bidirectional) | 5 |