The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Nanjing CIGU MODBUS RTU Controller. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Website: en.cigu.com.cn

HMI Settings

Parameters Recommended Options Notes
PLC type Nanjing CIGU MODBUS RTU Controller
PLC I/F RS485 2W
Baud rate 9600
Data bits 8
Parity None
Stop bits 1
PLC sta. no. 1

Device Address

Bit/Word Device type Format Range Memo
W 4x DDDD 1 ~ 3000

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-485 2W

HMI Direction PLC
Pin assignments RS485 2W
9P D-Sub
Male
Data- ↔ (bidirectional) 7 Data-
Data+ ↔ (bidirectional) 8 Data+
GND ↔ (bidirectional) 5 GND