Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Phoenix Contact ProConOS (Absolute Addressing). Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: KW ProConOS
HMI Settings
| Parameters | Recommended | Notes |
|---|---|---|
| PLC type | KW ProConOS (Absolute Addressing) | |
| PLC I/F | Ethernet | |
| Port no. | 20547 |
Device Address
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| B | IX | DDDDDo | 0 ~ 655357 | Input %IX |
| B | QX | DDDDDo | 0 ~ 655357 | Output %QX |
| B | MX | DDDDDDDDo | 0 ~ 518326727 | %MX |
| W | IW_EVEN | DDDDD | 0 ~ 65535 | %IW (must be even) |
| W | QW_EVEN | DDDDD | 0 ~ 65535 | %QW (must be even) |
| W | MW_EVEN | DDDDDDDD | 0 ~ 51832672 | %MW (must be even) |
| DW | ID_EVEN | DDDDD | 0 ~ 65535 | %ID (must be even) |
| DW | QD_EVEN | DDDDD | 0 ~ 65535 | %QD (must be even) |
| DW | MD_EVEN | DDDDDDDD | 0 ~ 51832672 | %MD (must be even) |
| Byte | IB | DDDDD | 0 ~ 65535 | |
| Byte | QB | DDDDD | 0 ~ 65535 | |
| Byte | MB | DDDDDDDD | 0 ~ 51832672 | |
| W | IW | DDDDD | 0 ~ 65535 | %IW |
| W | QW | DDDDD | 0 ~ 65535 | %QW |
| W | MW | DDDDDDDD | 0 ~ 51832672 | %MW |
| DW | ID | DDDDD | 0 ~ 65535 | %ID |
| DW | QD | DDDDD | 0 ~ 65535 | %QD |
| DW | MD | DDDDDDDD | 0 ~ 51832672 | %MD |
| W | STRING | DDDDDDDD | 0 ~ 51832672 |
Wiring Diagram
The diagram below shows the Ethernet cable wiring.