All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Keyence KV-3000. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: KEYENCE KV-3000

Website: www.keyence.com

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeKEYENCE KV-3000
PLC I/FRS232
Baud rate9600
Data bits8
ParityEven
Stop bits1
PLC sta. no.0

NOTE: Supports communications between HMI and PLC in pass-through mode.

Set LW-9903 to 2 to enhance the speed of download/upload PLC program in pass-through mode.

PLC Settings

ParameterValue
Communication modeKV STUDIO mode

Device Address

Bit/WordDevice TypeFormatRangeMemo
BMRDDDdd0 ~ 99915Internal auxiliary relay
BLRDDDdd0 ~ 99915Latch relay
BCRDDDdd0 ~ 99915Control relay
BRDDDdd0 ~ 99915Relay
BBHHHh0 ~ 3FFFLink relay
BTDDDD0 ~ 9999Timer
BCDDDD0 ~ 9999Counter
BDM_BitDDDDDdd0 ~ 6553515
BTM_BitDDDDdd0 ~ 999915
BCM_BitDDDDDdd0 ~ 6553515
BEM_BitDDDDDdd0 ~ 6553515
BFM_BitDDDDDdd0 ~ 6553515
WDMDDDDD0 ~ 65535Data memory
WTMDDDD0 ~ 9999Temp data memory
WCMDDDDD0 ~ 65535Control memory
WEMDDDDD0 ~ 65535Data memory
WFMDDDDD0 ~ 65535File register
WMR_WordDDD0 ~ 999
WLR_WordDDD0 ~ 999
WCR_WordDDD0 ~ 999
WWHHHH0 ~ 3FFFLink register
WZFDDDDDD0 ~ 131071File register
DWTCDDDD0 ~ 9999Timer current value
DWTSDDDD0 ~ 9999Timer set value
DWCCDDDD0 ~ 9999Counter current value
DWCSDDDD0 ~ 9999Counter set value
DWZDD1 ~ 12
DWTRMD0 ~ 7

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-232

Keyence KV-3000 programming port RJ connector showing 6 pins numbered 1 through 6.
HMIDirectionPLC
Pin assignmentsRS232
6P RJ11
Male
Rx↔ (bidirectional)2 SD
Tx↔ (bidirectional)4 RD
GND↔ (bidirectional)3 SG