All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Keyence KV-L20V/700/1000/3000/5000/Nano Series (KV Studio Mode). Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported series: KV-L20V, 700, 1000, 3000, 5000 series, KV Nano series

Website: keyence.com

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeKEYENCE KV-L20V/700/1000/3000/5000/Nano Series (KV Studio Mode)
PLC I/FRS232RS232, RS485 2W, RS485 4W
Baud rate1152009600 ~ 115200
Data bits8
ParityEven
Stop bits1
PLC sta. no.0
Online simulatorYES
Extend address modeNO

PLC Setting

ParameterValue
Communication modeKV STUDIO mode

Device Address

Bit/WordDevice TypeFormatRangeMemo
BMRDDDdd0 ~ 99915
BLRDDDdd0 ~ 99915
BCRDDDdd0 ~ 99915
BRDDDdd0 ~ 99915
BBHHHh0 ~ 3FFF
BTDDDD0 ~ 9999
BCDDDD0 ~ 9999
BDM_BitDDDDDdd0 ~ 6553515
BTM_BitDDDDdd0 ~ 999915
BCM_BitDDDDDdd0 ~ 6553515
BCTC_BitDdd0 ~ 315
BW_BitHHHHh0 ~ 3FFFF
BVM_BitDDDDDdd0 ~ 6553515
BVB_BitHHHh0 ~ 3FFF
WDMDDDDD0 ~ 65535
WTMDDDD0 ~ 9999
WCMDDDDD0 ~ 65535
WEMDDDDD0 ~ 65535
WFMDDDDD0 ~ 65535
WMR_WordDDD0 ~ 999
WLR_WordDDD0 ~ 999
WCR_WordDDD0 ~ 999
WWHHHH0 ~ 3FFF
WVMDDDDD0 ~ 65535
WVBHHH0 ~ 3FFF
WR_WordDDD0 ~ 999
WB_WordHHH0 ~ 3FF
WTCDDDD0 ~ 9999
WTSDDDD0 ~ 9999
WCCDDDD0 ~ 9999
WCSDDDD0 ~ 9999
DWCTHD0 ~ 1
DWCTCD0 ~ 3
DWZ_DWORDDD1 ~ 12

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-232 (OP-26486 9P RS232)

HMIDirectionPLC
Pin assignmentsOP-26486
9P D-Sub
Male
Rx↔ (bidirectional)3
Tx↔ (bidirectional)2
GND↔ (bidirectional)5

Diagram 2: RS-232 (KV-L20V Port2 RS232 Terminal)

HMIDirectionPLC
Pin assignmentsKV-L20V Port2
RS232 terminal
Rx↔ (bidirectional)3
Tx↔ (bidirectional)5
GND↔ (bidirectional)1

Diagram 3: RS-485 2W (KV-L20V Port2 RS485 2W)

HMIDirectionPLC
Pin assignmentsKV-L20V Port2
RS485 2W terminal
Data-↔ (bidirectional)3
Data+↔ (bidirectional)5
GND↔ (bidirectional)1

Diagram 4: RS-485 4W (KV-L20V Port2 RS485 4W Terminal)

HMIDirectionPLC
Pin assignmentsKV-L20V Port2
RS485 4W terminal
Rx-↔ (bidirectional)3
Rx+↔ (bidirectional)5
Tx-↔ (bidirectional)2
Tx+↔ (bidirectional)4
GND↔ (bidirectional)1

Diagram 5: RS-232 (RJ11 6P RS232)

Keyence KV L20V/700/1000/3000/5000/Nano series programming port RJ connector showing 6 pins numbered 1 through 6, KV Studio mode.
HMIDirectionPLC
Pin assignmentsRS232
6P RJ11
Male
Rx↔ (bidirectional)2 SD
Tx↔ (bidirectional)4 RD