Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Inovance H3U Series. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Website: http://www.inovance.cn/
HMI Settings
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | Inovance H3U Series | ||
| PLC I/F | RS485 4W | ||
| Baud rate | 9600 | 9600~19200 | |
| Data bits | 7 | 7 or 8 | |
| Parity | Even | Even, Odd, None | |
| Stop bits | 1 | 1 or 2 | |
| PLC sta. no. | 0 |
Device Address
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| B | X | OOO | 0 ~ 377 | |
| B | Y | OOO | 0 ~ 377 | |
| B | M | DDDD | 0 ~ 7999 | |
| B | M8000 | DDDD | 8000 ~ 8511 | |
| B | C_Bit | DDD | 0 ~ 255 | |
| B | T_Bit | DDD | 0 ~ 511 | |
| B | S | DDDD | 0 ~ 4095 | |
| B | SM | DDDD | 0 ~ 1023 | |
| W | C | DDD | 0 ~ 199 | |
| DW | C_Double | DDD | 200 ~ 255 | |
| W | T | DDD | 0 ~ 511 | |
| W | D | DDDD | 0 ~ 7999 | |
| W | D8000 | DDDD | 8000 ~ 8511 | |
| W | SD | DDDD | 0 ~ 1023 | |
| W | R | DDDDD | 0 ~ 32767 |
NOTE: ddd: Decimal, hhh: Hexadecimal, ooo: Octal.
Wiring Diagrams
NOTE: The serial port pin assignments may vary between HMI models.

The view from the soldering point of a connector.
RS-485 4W
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | H3U RS422 8P Mini-DIN Male | |
| Rx- | ↔ (bidirectional) | 4 |
| RX+ | ↔ (bidirectional) | 7 |
| Tx- | ↔ (bidirectional) | 1 |
| Tx+ | ↔ (bidirectional) | 2 |
| GND | ↔ (bidirectional) | 3 |