All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Inovance H2U/H1U. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Website: www.inovance.cn

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeInovance H2U/H1U
PLC I/FRS485 4W
Baud rate96009600~19200
Data bits77 or 8
ParityEvenEven, Odd, None
Stop bits11 or 2
PLC sta. no.0

Device Address

Bit/WordDevice typeFormatRangeMemo
BXOOO0 ~ 377Input Bits
BYOOO0 ~ 377Output Bits
BMDDDD0 ~ 7999Auxiliary Relay
BTDDD0 ~ 255Timer Relay
BCDDD0 ~ 255Counter Relay
BSMDDDD8000 ~ 9999Special Auxiliary Relay
BD_BitDDDDdd0 ~ 799915
BSDDDD0 ~ 4095
WTVDDD0 ~ 255Timer Memory
WCVDDD0 ~ 199Counter Memory
WDDDDD0 ~ 7999Data Registers
DWCV2DDD200 ~ 255Counter Memory (32bit)
WSDDDDD8000 ~ 9999Special Data Register

NOTE: ddd: Decimal, hhh: Hexadecimal, ooo: Octal.

Each model of CPU is different; refer to the PLC Manual Device List.

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-485 4W

8-pin circular DIN connector pinout for Inovance H2U/H1U series serial programming port, pins numbered 1 through 8.

The view from the soldering point of a connector

HMIDirectionPLC
Pin assignmentsH2U/H1U RS422
8P Mini-DIN Male
Rx-↔ (bidirectional)4
RX+↔ (bidirectional)7
Tx-↔ (bidirectional)1
Tx+↔ (bidirectional)2
GND↔ (bidirectional)3