The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Haiwell PLC. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Support Series: Haiwell A Series, C series, T Series, H Series, N Series, S Series PLC

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeHaiwell PLC
PLC I/FRS232RS232, RS485 2W
Baud rate1920019200
Data bits88
ParityNoneNone
Stop bits22
PLC sta. no.11~247

Device Address

Bit/WordDevice TypeFormatRangeMemo
BXDDDD0 ~ 1023Input Switch
BYDDDD0 ~ 1023Output Switch
BMDDDDD0 ~ 12287Internal Relay
BTDDDD0 ~ 1023Timer (Output Coil State)
BCDDD0 ~ 255Counter (Output Coil State)
BSMDDD0 ~ 215System Status Bit
BSDDDD0 ~ 2047Step Bit
WCRDD0 ~ 79Special Module Parameter Register
WAIDDD0 ~ 255Analog Input Register
WAQDDD0 ~ 255Analog Output Register
WVDDDDD0 ~ 14847Data Register
WTCVDDDD0 ~ 1023Timer (current value register)
WCCVDDD0 ~ 255Counter (current value register)
WSVDDD0 ~ 154System Register

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

RS-232 (RS232 4P Mini-Din)

The following is the view from the soldering point of a connector.

4-pin circular DIN connector for Haiwell PLC RS-232 serial port with pins numbered 1 through 4.
HMIDirectionPLC
Pin assignmentsRS232
4P Mini-Din
Male
Rx↔ (bidirectional)2
Tx↔ (bidirectional)1
GND↔ (bidirectional)3

RS-485 2W

HMIDirectionPLC
Pin assignmentsRS485 2W
Terminal
Data-↔ (bidirectional)B-
Data+↔ (bidirectional)A+
GND↔ (bidirectional)