Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Emotiontek MCU Controller. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: Emotiontek MCU-XP/XP2 Controller
Website: http://www.emotiontek.com
HMI Setting
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | Emotiontek MCU Controller | ||
| PLC I/F | RS232 | RS232/RS485 2W | |
| Baud rate | 38400 | 9600 ~ 115200 | |
| Data bits | 8 | 7,8 | |
| Parity | None | None,Odd,Even | |
| Stop bits | 1 | 1,2 | |
| PLC sta. no. | 0 | 0-255 |
PLC Setting
| Parameters | Value |
|---|---|
| Protocol type | 1,4 |
Device Address
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| B | X_Bit | Hh | 0 ~ 5f | |
| B | Y_Bit | Hh | 0 ~ 4f | |
| B | F_Bit | Dh | 0 ~ 9f | |
| B | M_Bit | DDDh | 0 ~ 199f | |
| B | T_Bit | Dh | 0 ~ 0f | |
| B | C_Bit | Dh | 0 ~ 0f | |
| W | X | D | 0 ~ 5 | |
| W | Y | D | 0 ~ 4 | |
| W | F | D | 0 ~ 9 | |
| W | M | DDD | 0 ~ 199 | |
| W | T | D | 0 | |
| W | C | D | 0 | |
| W | TP | DD | 0 ~ 15 | |
| W | TC | DD | 0 ~ 15 | |
| W | CP | DD | 0 ~ 15 | |
| W | CC | DD | 0 ~ 15 | |
| DW | PD_X | DD | 0 ~ 99 | |
| DW | PD_Y | DD | 0 ~ 99 | |
| DW | FD | D | 0 ~ 9 | |
| DW | DD | D | 0 ~ 9 | |
| DW | LD | DDDD | 0 ~ 1999 |
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
Diagram 1: RS-232
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS232 9P D-Sub Male |
|
| Rx | ↔ (bidirectional) | 3 TX |
| Tx | ↔ (bidirectional) | 2 RX |
| GND | ↔ (bidirectional) | 5 GND |
Diagram 2: RS-485 2W
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS485 2W 9P D-Sub Male |
|
| Data- | ↔ (bidirectional) | 8 Data- |
| Data+ | ↔ (bidirectional) | 7 Data+ |
| GND | ↔ (bidirectional) | 5 GND |