Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Artrich Inverter AR200/216/600 Series. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: Artrich Inverter AR200/216/600 Series
Website: www.artrich.cn
HMI Setting
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | Artrich Inverter AR200/216/600 Series | ||
| PLC I/F | RS485 2W | ||
| Baud rate | 9600 | ||
| Data bits | 8 | ||
| Parity | None | ||
| Stop bits | 1 | ||
| PLC sta. no. | 1 |
Device Address
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| B | F3002_bit |
Hh | 0 ~ 0f | |
| B | F3003_bit |
Hh | 0 ~ 0f | |
| W | F0-0 ~ F0-1 |
D | 0 | W/R |
| W | F0-2 |
D | 0 ~ 1 | W/R *Note1 |
| W | F0-3 ~ F0-178 |
D | 0 | W/R |
| W | F2-0 ~ F2-16 |
D | 0 | Read only |
| W | F3000 ~ F3001 |
D | 0 | Write only |
| W | F3002 ~ F3003 |
D | 0 | Read only |
| W | FC01 ~ FC12 |
D | 0 | Read only |
NOTE: *Note1 Value 0 means write to NAND Flash (Data will be saved after power off.) Value 1 means write to RAM (Data will not be saved after power off.)
Wiring Diagram
NOTE: The serial port pin assignments may vary between HMI models.
Diagram 1: RS-485 2W (8P RJ45)
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS485 2W 8P RJ45 | |
| Data- | ↔ (bidirectional) | 8 Data- |
| Data+ | ↔ (bidirectional) | 1 Data+ |
| GND | ↔ (bidirectional) |
Diagram 2: RS-485 2W
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS485 2W Terminal | |
| Data- | ↔ (bidirectional) | RS485- |
| Data+ | ↔ (bidirectional) | RS485+ |
| GND | ↔ (bidirectional) | GND |