The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Beckhoff ADS/AMS (Ethernet). Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: Twincat

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeBeckhoff ADS/AMS (Ethernet)
PLC I/FEthernet
Port no.48898
ADS port801801, 811, 821, 831
PLC sta. no.1

PLC Settings

In TwinCAT System Manager, while connected to the PLC, click on [Route Settings] and in the [Static Routes] subwindow press [Add].

TwinCAT System Manager showing Route Settings selected in the left panel and the Static Routes tab with the HMI route listed; the Add button is highlighted.

A new window will appear in which you must enter the following data:

  • Route Name: HMI or TP, or any name you prefer — it has no greater importance.
  • AMSNetID: The IP of the HMI followed by .1.1 — for example, 169.254.170.163.1.1
  • Transport Type: TCP/IP
  • Address Info: The IP of the HMI — for example, 169.254.170.163
  • Check Box: IP address
  • Click [Add Route]
TwinCAT System Manager Add Route dialog with Route Name set to HMI, AMS NetID showing 169.254.170.163.1.1, Transport Type TCP/IP, and Address Info filled with the HMI IP address.

In EBPro (EasyBuilder Pro), configure communication with the PLC using the PLC’s IP address and AMS NetID, then import the tags. In this example the PLC has IP 169.254.170.162 and AMS NetID 5:100:113:130:1:1.

EBPro (EasyBuilder Pro) device configuration dialog showing the IP address, IP port, ADS port set to 801, and the AMS NetID fields for the Beckhoff TwinCAT PLC connection.
EBPro (EasyBuilder Pro) Import Tags dialog with the Import Files – TwinCAT2 option selected from the list of available tag importer types.

Once you verify that everything works correctly, in TwinCAT System Manager activate the configuration on the PLC by pressing the Rubik’s cube button or via [Actions] > [Save in record…]. If this step is not completed, the PLC configuration is lost — the HMI route address you entered will not be saved to persistent memory.

TwinCAT System Manager showing the Activate la configuración tab with both the HMI and TONI-AB routes listed in the Static Routes table.

Device Address

Bit/WordDevice TypeFormatRangeMemo
BIXDDDDDo0 ~ 655357o : Bit no. (0 ~ 7)
BQXDDDDDo0 ~ 655357o : Bit no. (0 ~ 7)
BMXDDDDDo0 ~ 655357o : Bit no. (0 ~ 7)
WIWDDDDD0 ~ 65535
WQWDDDDD0 ~ 65535
WMWDDDDD0 ~ 65535
DWIDDDDDD0 ~ 65535
DWQDDDDDD0 ~ 65535
DWMDDDDDD0 ~ 65535

Support Device Type

Data TypeEBPro (EasyBuilder) Data FormatMemo
Boolbit
Word16-bit BCD, Hex, Binary, Unsigned16-bit
Int16-bit BCD, Hex, Binary, Signed16-bit
UInt16-bit BCD, Hex, Binary, Unsigned16-bit
DWord32-bit BCD, Hex, Binary, Unsigned32-bit
DInt32-bit BCD, Hex, Binary, Signed32-bit
Real32-bit Float32-bit
UDInt32-bit BCD, Hex, Binary, Unsigned32-bit

Wiring Diagram

The diagram below shows the Ethernet cable wiring.

Ethernet cable wiring diagram showing the color-coded wire pairs — W/Orange, Orange, W/Green, Blue, W/Blue, Green, W/Brown, Brown — connected pin-for-pin on both ends.