The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Toshiba Machine Provisor TC200. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: TOSHIBA MACHINE CO., JAPAN, TCMini

Website: http://www.toshiba-machine.co.jp

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeTOSHIBA MACHINE Provisor TC200
PLC I/FRS232RS232In accordance with PLC port
Baud rate96009600, 19200
Data bits87, 8
ParityNoneEven, Odd, None
Stop bits11, 2

Device Address

Bit/WordDeviceFormatRangeMemo
BR_bitHHHh0 ~ ffffh : Bit no.(0~f)
BX_bitHHHh0 ~ ffffh : Bit no.(0~f)
BY_bitHHHh0 ~ ffffh : Bit no.(0~f)
BL_bitHHHh0 ~ ffffh : Bit no.(0~f)
BG_bitHHHh0 ~ ffffh : Bit no.(0~f)
BH_bitHHHh0 ~ ffffh : Bit no.(0~f)
BT_bitHHHh0 ~ ffffh : Bit no.(0~f)
BC_bitHHHh0 ~ ffffh : Bit no.(0~f)
BS_bitHHHh0 ~ ffffh : Bit no.(0~f)
BE_bitHHHh0 ~ ffffh : Bit no.(0~f)
WPHHH0 ~ fff
WVHHH0 ~ fff
WXHHH0 ~ fff
WYHHH0 ~ fff0 ~ fff
WDHHH0 ~ fff
WRHHH0 ~ fff
WLHHH0 ~ fff
WBHHH0 ~ fff
WGHHH0 ~ fff
WHHHH0 ~ fff
WTHHH0 ~ fff
WCHHH0 ~ fff
WSHHH0 ~ fff
WEHHH0 ~ fff

Wiring Diagram

RS-232

NOTE: The serial port pin assignments may vary between HMI models.

HMIDirectionPLC
Pin assignmentsTC mini series
RS232
9P D-Sub
Male
Rx↔ (bidirectional)2 TX
Tx↔ (bidirectional)3 RX
GND↔ (bidirectional)5 GND
↕︎ (tie)7
8