All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Kernel Sistemi DMX Series. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: Kernel systemi DMX 30

Website: http://www.kernelgroup.it/

HMI Settings

Parameters Recommended Options Notes
PLC type Kernel Sistemi DMX Series
PLC I/F RS232 RS485
Baud rate 19200 9600
Data bits 8
Parity None
Stop bits 1
PLC sta. no. 1 Must match the PLC port setting

Device Address

Bit/Word Device type Format Range Memo
W D HHHH 0 ~ ffff

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-232

HMI Direction PLC
Pin assignments DMX30 RS232
9P D-Sub
Male
Rx ↔ (bidirectional) 3
Tx ↔ (bidirectional) 2
GND ↔ (bidirectional) 5