The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with OuHua OHJX. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeOuHua OHJX
PLC I/FRS-232
Baud rate96009600, 19200
Data bits8
ParityOdd
Stop bits1
PLC sta. no.1

Device Address

Bit/WordDevice typeFormatRangeMemo
BR100Dh0 ~ 1f
BR101Dh0 ~ 1f
BR102Dh0 ~ 1f
BR103Dh0 ~ 1f
BR104Dh0 ~ 1f
BR105Dh0 ~ 1f
BR106Dh0 ~ 1f
BR107Dh0 ~ 1f
BR108Dh0 ~ 1f
BR109Dh0 ~ 1f
BR110Dh0 ~ 1f
BR210Dh0 ~ 1f
BR310Dh0 ~ 1f
BR_BitDDDDh0 ~ 9999f
WSVDDDD0 ~ 9999
WEVDDDDD0 ~ 65535
WDTDDDDD0 ~ 99999
WLDDDDD0 ~ 8447
WWXDDDD0 ~ 9999
WWYDDDD0 ~ 9999
WWRDDDD0 ~ 9999
WWLDDDD0 ~ 9999
WFLDDDDD0 ~ 99999

Wiring Diagram

NOTE: The serial port pin assignments may vary between HMI models.

RS-232

4-pin Mini-DIN Male connector face view showing pin positions: 1 top-left, 4 top-right, 2 bottom-left, 3 bottom-right.

The view from the soldering point of a connector.

HMIDirectionPLC
Pin assignments4P Mini-DIN Male
Rx↔ (bidirectional)3 TX
Tx↔ (bidirectional)2 RX
GND↔ (bidirectional)1 GND
↕︎ (tie)4 GND