Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with ODVA General EtherNet/IP (Implicit Messaging). Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: ODVA General EtherNet/IP Implicit Messaging Device
HMI Setting
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | ODVA General EtherNet/IP | ||
| PLC I/F | Ethernet | ||
| Port no. | 44818 | ||
| Assembly instance | Input: 101 Output: 111 Config: 0 | Max: 512 Byte (Input) Max: 512 Byte (Output) | |
| Multicast | Disable | Disable / Enable | |
| Electronic key | None | Use / None | |
| Online simulator | YES | ||
| Multiple device connections | NO |
Standard Production Data

Parameter Settings

Device Address
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| B | Input_Bit | DDDdd | 0 ~ 51215 | |
| B | Output_Bit | DDDdd | 0 ~ 51215 | |
| W | Input | DDD | 0 ~ 512 | |
| W | Output | DDD | 0 ~ 512 |
Wiring Diagram
The diagram below shows the Ethernet cable wiring.