The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with a Mitsubishi Q06H. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: Mitsubishi Q06H CPU port

Website: http://www.mitsubishi-automation.com

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeMitsubishi Q06H
PLC I/FRS232RS485 4W, RS232
Baud rate115200115200 only
Data bits8
ParityOdd
Stop bits1
PLC sta. no.0
Online simulatorYES
Extend address modeNO
Broadcast commandNO

NOTE: Supports communications between HMI and PLC in pass-through mode.

NOTE: Set LW-9903 to 2 to enhance the speed of download/upload PLC program in pass-through mode.

Device Address

Bit/WordDevice TypeFormatRangeMemo
BSMDDDD0 ~ 2047
BXHHHH0 ~ 1fffInput Relay
BYHHHH0 ~ 1fffOutput Relay
BMDDDDD0 ~ 61439Internal Relay
BLDDDDD0 ~ 32767Latch Relay
BFDDDDD0 ~ 32767Annunciator
BVDDDDD0 ~ 32767Edge Relay
BBHHHH0 ~ 7fffLink Relay
BTCDDDDD0 ~ 23087Timer Coil
BSSDDDDD0 ~ 23087Retentive Timer
BSCDDDDD0 ~ 23087Retentive Timer Coil
BCSDDDDD0 ~ 23087Counter Contact
BCCDDDDD0 ~ 23087Counter Coil
BSBHHH0 ~ 7ffSpecial Link Relay
BSDDDD0 ~ 8191Step Relay
BDXHHHH0 ~ 1fffDirect Input
BDYHHHH0 ~ 1fffDirect Output
BTSDDDD0 ~ 2047Timer Contact
BD_BitDDDDDDDh0 ~ 4212735f
BZR_BitHHHHHh0 ~ fe7fff
BZR_Dec_BitDDDDDDDh0 ~ 1042431f
WWHHHH0 ~ 657fLink Register
WTNDDDDD0 ~ 23087Timer Current Value
WSNDDDDD0 ~ 23087Retentive Timer
WCNDDDDD0 ~ 23087Counter Current Value
WRFFDDDDD0 ~ 3132767File Register (FF:File No. 0~31)(DDDDD:0~32767)
WSWHHH0 ~ 7ffSpecial Link Register
WZDD0 ~ 15Index Register
WZRHHHHH0 ~ fe7ffFile Register
WZR_decimal_addrDDDDDDD0 ~ 1042431
WDDDDDD0 ~ 25983Data Register

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

The following is the view from the soldering point of a connector.

Wiring diagram for Mitsubishi Q-Series CPU RS-232 port using a 6P Mini-DIN Male connector, showing HMI Rx, Tx, and GND connections to PLC pins 1, 2, and 4.

RS-232: 6P Mini-DIN: Q02 CPU Port

HMIDirectionPLC
Pin assignmentsRS232
6P Mini-DIN
Male
Rx↔ (bidirectional)1
Tx↔ (bidirectional)2
GND↔ (bidirectional)4
↕︎ (tie)5
6