The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with a Mitsubishi FX3U/FX3G. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: Mitsubishi FX3U/FX3UC/FX3G/FX3S

Website: http://www.mitsubishi-automation.com

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeMitsubishi FX3U/FX3G
PLC I/FRS485 4wRS232 / RS485 2w/4w / USB
Baud rate384009600/19200
Data bits7
ParityEven
Stop bits1
PLC sta. no.0Does not apply to this protocol
Online simulatorYES (9600 baud rate only)
Extend address modeNO

NOTE: Support communications between HMI and PLC in pass-through mode.

NOTE: Set LW-9903 to 2 to enhance the speed of download/upload PLC program in pass-through mode.

Device Address

Bit/WordDeviceFormatRangeMemo
BXOOO0 ~ 764Input Relay
BYOOO0 ~ 764Output Relay
BMDDDD0 ~ 7999Auxiliary Relay
BTDDD0 ~ 511Timer Relay (T)
BCDDD0 ~ 255Counter Relay (C)
BSMDDDD8000 ~ 9999Special Relay (M)
BD_BitDDDDdd0 ~ 799915Data Register Bit (D)
BSDDDD0 ~ 4095State Relay (S)
WTVDDD0 ~ 511Timer Memory (T)
WCVDDD0 ~ 199Counter Memory (C)
WDDDDD0 ~ 7999Data Register (D)
DWCV2DDD200 ~ 255Counter Memory (D Word)
WSDDDDD8000 ~ 9999Special Data Register (D)
WRDDDDD0 ~ 32767Extended Register (R)
WZD0 ~ 7Index register

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

The following is the view from the soldering point of a connector.

8P Mini-Din male connector pinout diagram showing pin numbering for the Mitsubishi FX3U RS-422 port.

RS-485 4W

HMIDirectionPLC
Pin assignmentsRS422
Port 8P Mini-Din
Male
Rx-↔ (bidirectional)4
RX+↔ (bidirectional)7
Tx-↔ (bidirectional)1
Tx+↔ (bidirectional)2
GND↔ (bidirectional)3