Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with a Mitsubishi FX232/485BD. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: Mitsubishi FX0N/FX2/FX2N COM for Communication Module BD FX2N-485-BD, FX2N-232-BD, FX1N-485-BD, FX1N-232-BD, FX3U-485-ADP/BD.
HMI Settings
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | Mitsubishi FX232/485BD | ||
| PLC I/F | RS232/RS485 | RS232/RS485 2w/4w | In accordance with the BD module |
| Baud rate | 19200 | 9600/19200/38400 | |
| Data bits | 7 | 7, 8 | |
| Parity | Even | Even, Odd, None | |
| Stop bits | 1 | 1, 2 | |
| PLC sta. no. | 1 | 0–15 | |
| Online simulator | YES | ||
| Extend address mode | YES | ||
| Pass-Through | No |
NOTE: It is recommended to set turn around delay to 8 (for RS-485 2W).
PLC Settings
Must set PLC station when using BD Module.
Register D8120 setting: set b9 and b8 of BFM#0 to 0.
FX2N-485-BD / FX1N-485-BD

FX2N-232-BD / FX1N-232-BD

Device Address
| Bit/Word | Device Type | Format | Range | Memo |
|---|---|---|---|---|
| B | X | OOO | 0 ~ 377 | Input Relay |
| B | Y | OOO | 0 ~ 377 | Output Relay |
| B | M | DDDD | 0 ~ 7999 | Auxiliary Relay |
| B | T | DDD | 0 ~ 511 | Timer Relay |
| B | C | DDD | 0 ~ 255 | Counter Relay |
| B | SM | DDDD | 8000 ~ 9999 | Special Auxiliary Relay |
| B | D_Bit | DDDDh | 0 ~ 7999f | Data Register Bit |
| B | S | DDDD | 0 ~ 4095 | State Relay |
| W | TV | DDD | 0 ~ 511 | Timer Memory |
| W | CV | DDD | 0 ~ 199 | Counter Memory |
| W | D | DDDD | 0 ~ 7999 | Data Register |
| W | CV2 | DDD | 200 ~ 255 | Counter Memory (D Word) |
| W | SD | DDDD | 8000 ~ 9999 | Special Data Register |
| W | R | DDDDD | 0 ~ 32767 | Extended Register |
Wiring Diagrams
NOTE: The serial port pin assignments may vary between HMI models.
Diagram 1: RS-232 (Communication Module RS232-BD)
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | RS232 9P D-Sub Male | |
| Rx | ↔ (bidirectional) | 3 |
| Tx | ↔ (bidirectional) | 2 |
| GND | ↔ (bidirectional) | 5 |
Diagram 2: RS-485 4W (Communication Module RS485-BD)
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | 485BD Module 5P Terminal | |
| Rx- | ↔ (bidirectional) | SDB |
| RX+ | ↔ (bidirectional) | SDA |
| Tx- | ↔ (bidirectional) | RDB |
| Tx+ | ↔ (bidirectional) | RDA |
| GND | ↔ (bidirectional) | GND |
Diagram 3: RS-485 2W (Communication Module RS485-BD)
| HMI | Direction | PLC |
|---|---|---|
| Pin assignments | 485BD Module 5P Terminal | |
| Data- | ↔ (bidirectional) | SDB |
| ↕︎ (tie) | RDB | |
| Data+ | ↔ (bidirectional) | SDA |
| ↕︎ (tie) | RDA | |
| GND | ↔ (bidirectional) | SG |