The leader in industrial automation and control solutions

Introduction

All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with a Mitsubishi AJ71 (Format 4). Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: Mitsubishi A series PLC with AJ71C24 communication module using the Computer Link protocol.

Website: http://www.mitsubishi-automation.com

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeMitsubishi AJ71 (Format 4)
PLC I/FRS485 4WRS485 4W, RS232
Baud rate192009600, 19200
Data bits88
ParityEvenEven, Odd, None
Stop bits11
PLC sta. no.0

PLC Settings

ParameterValue
Communication modeComputer Link protocol 9600, Even, 8, 1 (default)
Mode setting switchFormat 4
Parity checkEnable
Sum checkEnable

Device Address

Bit/WordDevice typeFormatRangeMemo
BXHHHH0 ~ ffffInput Bits
BYHHHH0 ~ ffffOutput Bits
BMDDDDD0 ~ 65535Internal Relays
BTDDDDD0 ~ 65535
BCDDDDD0 ~ 65535
BBHHHH0 ~ ffff
BFDDDDD0 ~ 65535
WTVDDDDD0 ~ 65535Timer Preset Value
WCVDDDDD0 ~ 65535Counter Preset Value
WDDDDDD0 ~ 65535Data Registers
WWHHHH0 ~ ffff
WRDDDDD0 ~ 65535

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

RS-485 4W

HMIDirectionPLC
Pin assignmentsAJ71C24 RS422 Terminal
Rx-↔ (bidirectional)SDB
RX+↔ (bidirectional)SDA
Tx-↔ (bidirectional)RDB
Tx+↔ (bidirectional)RDA
GND↔ (bidirectional)GND

RS-232

HMIDirectionPLC
Pin assignmentsRS232 9P D-Sub Male
Rx↔ (bidirectional)TXD-3
Tx↔ (bidirectional)RXD-2
GND↔ (bidirectional)GND-5
↕︎ (tie)DCD-1
DTR-4
DSR-6
↕︎ (tie)RTS-7
CTS-8