All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with HCFA R Series. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: HCFA R Series

Website: https://www.hcfa.cn/

HMI Settings

ParametersRecommendedOptionsNotes
PLC typeHCFA R Series
PLC I/FRS485 2WRS232 / RS-485 4W
Baud rate9600 ~ 115200
Data bits8
ParityNone
Stop bits1
PLC sta. no.11 ~ 247

Device Address

Bit/WordDevice typeFormatRange
BXOOO0 ~ 377
BYOOO0 ~ 377
BMDDDDD0 ~ 10239
BFDDDDD0 ~ 10239
BSDDDDD0 ~ 10239
BLDDDDD0 ~ 10239
BSMDDDDD0 ~ 10239
BTCDDDDD0 ~ 10239
BTSDDDDD0 ~ 10239
BSTCDDDDD0 ~ 10239
BSTSDDDDD0 ~ 10239
BCCDDDDD0 ~ 10239
BCSDDDDD0 ~ 10239
BLCCDDDDD0 ~ 10239
BLCSDDDDD0 ~ 10239
WTVDDDDD0 ~ 10239
WSTVDDDDD0 ~ 10239
WCVDDDDD0 ~ 10239
WDDDDDD0 ~ 10239
WRDDDDD0 ~ 10239
WSDDDDDD0 ~ 16383
DWLCVDDDDD0 ~ 10239

Wiring Diagrams

NOTE: The serial port pin assignments may vary between HMI models.

Diagram 1: RS-485 2W

HMIDirectionPLC
Pin assignmentsRS485 2W
Terminal
Data-↔ (bidirectional)DB
Data+↔ (bidirectional)DA
GND↔ (bidirectional)GND

Diagram 2: RS-232

8-pin Mini-Din connector pinout diagram showing pin positions for connecting an HMI to the HCFA R Series PLC RS-232 port.
HMIDirectionPLC
Pin assignmentsRS232
8P Mini-Din
Male
Rx↔ (bidirectional)6
Tx↔ (bidirectional)8
GND↔ (bidirectional)5

Diagram 3: RS-485 4W

8-pin Mini-Din connector pinout diagram showing pin positions for connecting an HMI to the HCFA R Series PLC RS-485 4W port using RS-422.
HMIDirectionPLC
Pin assignmentsRS422
Port 8P Mini-Din
Male
Rx-↔ (bidirectional)4
RX+↔ (bidirectional)7
Tx-↔ (bidirectional)1
Tx+↔ (bidirectional)2
GND↔ (bidirectional)5