All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Elsist Modbus TCP/IP. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: SlimLine & Netsyst controllers Ethernet TCP/IP

Website: http://www.elsist.it

HMI Setting

ParametersRecommendedOptionsNotes
PLC typeELSIST MODBUS TCP/IP
PLC I/FEthernet
Port no.502
PLC sta. no.10~254 (255 Broadcast)

PLC Setting

Communication mode
Modbus TCP/IP

Device Address

Bit/WordDevice typeFormatRangeMemo
B%MXDDDDD1 ~ 655350x01 Read coil
0x05 write single coil
B%MW_BitDDDDDdd100 ~ 65535150x03 Read holding register
0x10 write single register
W%MWDDDDD1 ~ 655350x03 Read holding register
0x10 write multiple registers
DW%MDDDDDD1 ~ 655350x03 Read holding register
0x10 write multiple registers
LW%MLDDDDD1 ~ 65535

Wiring Diagram

The diagram below shows the Ethernet cable wiring.

Ethernet cable wiring diagram showing color-coded twisted pairs labeled 1 through 8, with W/Orange, Orange, W/Green, Blue, W/Blue, Green, W/Brown, and Brown on both ends.