Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with Elsist Modbus TCP/IP. Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: SlimLine & Netsyst controllers Ethernet TCP/IP
Website: http://www.elsist.it
HMI Setting
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | ELSIST MODBUS TCP/IP | ||
| PLC I/F | Ethernet | ||
| Port no. | 502 | ||
| PLC sta. no. | 1 | 0~254 (255 Broadcast) |
PLC Setting
| Communication mode |
|---|
| Modbus TCP/IP |
Device Address
| Bit/Word | Device type | Format | Range | Memo |
|---|---|---|---|---|
| B | %MX | DDDDD | 1 ~ 65535 | 0x01 Read coil 0x05 write single coil |
| B | %MW_Bit | DDDDDdd | 100 ~ 6553515 | 0x03 Read holding register 0x10 write single register |
| W | %MW | DDDDD | 1 ~ 65535 | 0x03 Read holding register 0x10 write multiple registers |
| DW | %MD | DDDDD | 1 ~ 65535 | 0x03 Read holding register 0x10 write multiple registers |
| LW | %ML | DDDDD | 1 ~ 65535 |
Wiring Diagram
The diagram below shows the Ethernet cable wiring.