Introduction
All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with a Mitsubishi M80 (Ethernet). Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.
Supported Series: Mitsubishi M80 (QJ71E71+Q26UDH CPU)
Website: http://www.mitsubishi-automation.com
HMI Settings
| Parameters | Recommended | Options | Notes |
|---|---|---|---|
| PLC type | Mitsubishi M80 (Ethernet) | ||
| PLC I/F | Ethernet | ||
| Port no. | 5002 | ||
| Online simulator | YES | ||
| EasyAccess 2.0 | YES |
Device Address
| Bit/Word | Device Type | Format | Range | Memo |
|---|---|---|---|---|
| B | X | HHHH | 0 ~ 1fff | |
| B | Y | HHHH | 0 ~ 1fff | |
| B | M | DDDDD | 0 ~ 61439 | |
| B | L | DDDD | 0 ~ 1023 | |
| B | F | DDDD | 0 ~ 2047 | |
| B | V | DDD | 0 ~ 511 | |
| B | B | HHHH | 0 ~ dfff | |
| B | SM | DDDD | 0 ~ 2047 | |
| B | SB | HHH | 0 ~ 3ff | |
| B | D_Bit | DDDDh | 0 ~ 4095f | h: bit no.(0~f) |
| B | ZR_Bit | DDDDDh | 0 ~ 13311f | h: bit no.(0~f) |
| B | TC | DDDD | 0 ~ 2047 | |
| B | TS | DDDD | 0 ~ 2047 | |
| B | CC | DDD | 0 ~ 511 | |
| B | CS | DDD | 0 ~ 511 | |
| B | STC | DDD | 0 ~ 127 | |
| B | STS | DDD | 0 ~ 127 | |
| B | D | DDDD | 0 ~ 4095 | |
| W | W | HHHH | 0 ~ 2fff | |
| W | SW | HHH | 0 ~ 3ff | |
| W | R | DDDDD | 0 ~ 32767 | |
| W | SD | DDDD | 0 ~ 2047 | |
| W | Z | DD | 0 ~ 19 | |
| W | ZR | DDDDD | 0 ~ 13311 | |
| W | TN | DDDD | 0 ~ 2047 | |
| W | CN | DDD | 0 ~ 511 | |
| W | STN | DDD | 0 ~ 127 |
Wiring Diagram
The diagram below shows the Ethernet cable wiring.