All Maple Systems HMIs programmed with EBPro (EasyBuilder Pro), including every cMT X Series and cMT Series model, are compatible with CO-TRUST CTH300-H (Ethernet). Configure your Controller and HMI/cMT with the following parameters to establish reliable communication.

Supported Series: CO-TRUST CTH300-H35

Website: http://en.co-trust.com/

HMI Setting

Parameters Recommended Options Notes
PLC type CO-TRUST CTH300-H (Ethernet)   Use UDP
PLC I/F Ethernet    
Port no. 1024    
PLC sta. no. 0    

Device Address

Bit/Word Device type Format Range Memo
B I DDDDo 0 ~ 40957 Input (I)
B Q DDDDo 0 ~ 40957 Output (O)
B M DDDDo 0 ~ 40957 Bit Memory
B VW_Bit DDDDDo 0 ~ 655347 V Memory Bit Address
B S DDDDo 0 ~ 40957 SCR
B SM DDDDo 0 ~ 40957 Special Memory
B T_Bit DDDD 0 ~ 1023 Timer
B C_Bit DDDD 0 ~ 1023 Counter
B DBnBit FFFDDDDDo 0 ~ 255655357  
Byte VB DDDDD 0 ~ 65535  
W VW DDDDD 0 ~ 65534 V Memory
W VW_Odd DDDDD 0 ~ 65534 V Memory
W VW_String DDDDD 0 ~ 65534 String
W VW_String_Odd DDDDD 0 ~ 65532 String
DW VD DDDDD 0 ~ 65532 V Memory Double
DW VD_Odd DDDDD 0 ~ 65532 V Memory Double
DW VD_String DDDDD 0 ~ 65532 String
DW VD_String_Odd DDDDD 0 ~ 65532 String
Byte MB DDDDD 0 ~ 10239 Byte Memory
W MW DDDDD 0 ~ 10239 Word Memory
W MW_Odd DDDDD 0 ~ 10239 Word Memory
DW MD DDDDD 0 ~ 10239 Word Memory
Byte SB DDDDD 0 ~ 10239 SCR
W SW DDDDD 0 ~ 10239 SCR
DW SD DDDDD 0 ~ 10239 SCR
Byte SMB DDDDD 0 ~ 10239 Special Memory
W SMW DDDDD 0 ~ 10239 Special Memory
DW SMD DDDDD 0 ~ 10239 Special Memory
W T DDD 0 ~ 1023 Timer
W C DDD 0 ~ 1023 Counter
Byte DBBn FFFDDDDD 0 ~ 25565535  
W DBn FFFDDDDD 0 ~ 25565535  
DW DBDn FFFDDDDD 0 ~ 25565535  
D DBn_STRINGCHAR FFFDDDDD 0 ~ 25565535  

NOTE: Double Word and floating point value must use VD device type.

Wiring Diagram

The diagram below shows the Ethernet cable wiring.