The leader in industrial automation and control solutions

How much available memory on the cMT CODESYS runtime?

Tags:

  • cMT
  • CODESYS
  • cMT X

The allocated memory for “Data, Input, Output, Memory, Code” is the maximum size of a CODESYS IDE project. Project files may not exceed the available memory on the cMT series’ CODESYS runtime, or else “Out of code memory…No download possible” errors will occur.

Memory limits on CODESYS firmware revisions prior to v20240703 are as follows:

SubsystemAvailable Memory
Data, Input, Output, Memory, Code3 MB
Retain area
(Data persisting after reboots)
16 KB
(Data is saved every 1 minute)
Persistent area
(Data persisting after project downloads)
16 KB
(Data is saved every 1 minute)
File system8 MB

Additional memory is available on cMT/cMT X series devices running version v20240703 or higher of the CODESYS firmware. Memory limits on CODESYS firmware revisions v20240703 and higher are as follows:

SubsystemAvailable Memory
Data, Input, Output, Memory, Code5 MB
Retain area
(Data persists after reboots)
32 KB
(Data is saved every 1 minute)
Persistent area
(Data persists after downloads)
32 KB
(Data is saved every 1 minute)
File system12 MB

NOTE: “CODESYS & Remote IO Package” version 1.5.3.500 or later must be used in CODESYS IDE for cMT/cMT X series devices is running CODESYS firmware v20240703 or higher.