How much available memory on the cMT CODESYS runtime?
The allocated memory for “Data, Input, Output, Memory, Code” is the maximum size of a CODESYS IDE project. Project files may not exceed the available memory on the cMT series’ CODESYS runtime, or else “Out of code memory…No download possible” errors will occur.
Memory limits on CODESYS firmware revisions prior to v20240703 are as follows:
Subsystem | Available Memory |
---|---|
Data, Input, Output, Memory, Code | 3 MB |
Retain area (Data persisting after reboots) | 16 KB (Data is saved every 1 minute) |
Persistent area (Data persisting after project downloads) | 16 KB (Data is saved every 1 minute) |
File system | 8 MB |
Additional memory is available on cMT/cMT X series devices running version v20240703 or higher of the CODESYS firmware. Memory limits on CODESYS firmware revisions v20240703 and higher are as follows:
Subsystem | Available Memory |
---|---|
Data, Input, Output, Memory, Code | 5 MB |
Retain area (Data persists after reboots) | 32 KB (Data is saved every 1 minute) |
Persistent area (Data persists after downloads) | 32 KB (Data is saved every 1 minute) |
File system | 12 MB |