The leader in industrial automation and control solutions

Applicable Model(s)

HMI5000 Series
cMT Series

Title

TCP Port Usage of HMI and cMT Products

Date

10/29/2024

Rev

02

P/N

0907-5127

Summary

Both the HMI 5000 Series as well as the cMT Series of devices use a number of Ethernet ports when doing various tasks. This document serves as a reference for these port numbers.


Solution

Many of the features for both the Graphic HMIs and the cMT Series products use Ethernet communication, often with a specified TCP port. Below is a table of the ports used and their respective feature:

HMI Series
TCP PortUsage
21Default port for the FTP server, can be changed in System Parameter Settings within EasyBuilder Pro project
443Communication with EasyAccess 2.0 servers
502Default port for Modbus TCP/IP Communication
2000Ethernet Pass-through functionality, can be changed in System Parameter Settings within EasyBuilder Pro project
80, 5800VNC server (over HTTP and Java)
5900Port for connecting to VNC server
8000Communication with Remote HMI, can be changed in System Parameter Settings within EasyBuilder Pro project
8001EasyDiagnoser communication
8005Used with EasyPrinter, can be changed in System Parameter Settings under Printer/Backup tab
8010Communication with Remote HMI, specifically between cMT series and HMI series devices. Can be changed in System Parameter settings under the Model tab
8080Used for Web Streaming on the P and XL models of the HMI 5000 series
10275Search for HMI feature
20248Default port for downloading an EasyBuilder Pro project file over ethernet, including over the open internet with the help of a VPN connection or Port Forwarding. Can be configured in the Download Menu under the Settings… menu
cMT Series
TCP PortUsage
21Default port for the FTP server, can be changed in System Parameter Settings within EasyBuilder Pro project
80, 443Default port for downloading an EasyBuilder Pro project file over ethernet, including over the open internet with the help of a VPN connection or Port Forwarding. Can be configured in the Download Menu under the Settings… menu
443Communication with EasyAccess 2.0 servers
502Default port for Modbus TCP/IP Communication
554Used for RTSP with IP Cameras
2000Ethernet Pass-through functionality, can be changed in System Parameter Settings within EasyBuilder Pro project
5800Used for WebView on the cMT-X series
5900Port for connecting to VNC server
8000Communication with Remote HMI, can be changed in System Parameter Settings within EasyBuilder Pro project
8001EasyDiagnoser communication
8002cMT Diagnoser communication
8005Used with EasyPrinter, can be changed in System Parameter Settings under Printer/Backup tab
8010Communication with Remote HMI, specifically between cMT series and HMI series devices. Can be changed in System Parameter settings under the Model tab
8080Used for Web Streaming on cMT-SVR models
9100Used with Common Unix Printing System (CUPS) for the cMT-3151
10275Search for HMI feature
10463cMT Diagnoser GUI
10763cMT GUI, cMT Viewer connection, and cMT Diagnoser connection. Affects User Access Control (UAC) and Trend/Event Display objects.