The leader in industrial automation and control solutions
Version: 20250212
  1. Added support for PROFINET Controller.
Version: 20240703

For cMT-CTRL01, please use with “CTRL Embedded iR Coupler Firmware” 1.02.0 or later.

  1. used b
Version: 20241206
  1. Fixed errors caused by specific operations.
  2. Fixed an issue where Watchdog may occasionally trigger incorrectly.
Version: 20240703

For cMT-CTRL01, please use with “CTRL Embedded iR Coupler Firmware” 1.02.0 or later.

  1. Added support for CAA components.
  2. Increased storage and memory space:
    • Data, Input, Output, Memory, Code: Increased from 3 MB to 5 MB
    • Retain area (retains data after restart): Increased from 16 KB to 32 KB
    • Persistent area (retains data after download): Increased from 16 KB to 32 KB
    • File System: Increased from 8 MB to 12 MB
  3. Increased the number of available CODESYS programming/communication channels to 16.
Version: 20240507

For cMT-CTRL01, please use with “CTRL Embedded iR Coupler Firmware” 1.02.0 or later.

  1. Fixed an issue where CODESYS activation status cannot be displayed correctly on cMT-FHDX and cMT-SVRX.
  2. Fixed communication issues that occur when the number of MODBUS slave devices exceeds 14.
  3. Optimized CODESYS LOG feature to improve system diagnostics capabilities.
Version: 20240204

For cMT-CTRL01, please use with “CTRL Embedded iR Coupler Firmware” 1.02.0 or later.

  1. Added support for EtherNet/IP.
  2. Added support for Recipe Manager.
  3. Added SysFileCopy() support for all current models.
  4. Added support for new library functions.
Version: 20220818

For cMT-CTRL01, please use with “CTRL Embedded iR Coupler Firmware” 1.02.0 or later.

  1. Increased the available CODESYS programming/communication channels to 12.
  2. Fixed an issue where the CODESYS runtime in cMT-CTRL01 might go into error state if its program attempts to access I/O data without I/O being physically attached.
Version: 20220407

For cMT-CTRL01, please use with “CTRL Embedded iR Coupler Firmware” 1.02.0 or later.

  1. Fixed an issue where CODESYS system clock (SysTimeRtc) runs a little slower.
Version: 20210913

For cMT-CTRL01, please use with “CTRL Embedded iR Coupler Firmware” 1.02.0 or later.

  1. Increased the available CODESYS programming/communication channels to 8.
Version: 20210119

For cMT-CTRL01, please use with “CTRL Embedded iR Coupler Firmware” 1.02.0 or later.

  1. Added support for
    • cMT X Standard: cMT2078X, cMT2108X, cMT2158X
    • cMT X Advanced: cMT3072X, cMT3072XH, cMT3102X
  2. Added SysFileCopy() function to copy file from/to external device (SD card, USB disk).
  3. Optimized iBus Data Exchange mechanism for cMT-CTRL01.
  4. Added iBus Read/Write function for cMT-CTRL01.
Version: 20200731
  1. Added support for cMT-FHDX.
  2. Added a mechanism for software update to prevent installation of CODESYS Firmware versions that are not applicable.
Version: 20200401
  1. Added support for EtherCAT Master.
Version: 20191206
  1. Fixed an issue where CODESYS Trace cannot be used via HMI’s Ethernet port.
Version: 20191025
  1. Optimized response time for cMT-CTRL01.
  2. Fixed an issue where, under certain circumstances, unwanted broadcast commands are sent when the device is connected by EBPro’s on-line simulation.
Version: 20190701
  1. Added support for cMT-CTRL01.
  2. Fixed an issue where Modbus does not work when LAN 1 is not connected via an Ethernet cable.
Version: 20181218
  1. Optimized system performance.
  2. Fixed runtime issues that might lead to system crashes.
Version: 20180807
  1. Improved system stability.
Version: 20180331
  1. First cMT + CODESYS release.