Indicators
System Indicators | Red LED Input State |
Communication
Connection Cross-section | AWG 28-16 |
Digital Input
Total Number of Inputs | 8 |
Input Logic | Sink or Source |
Response Time | OFF -> ON 5ms; ON -> OFF 1ms |
Input Impedance | 5.6 KΩ |
Current Consumption | 130mA@5VDC |
High Level Input Voltage | 15~28 VDC |
Low Level Input Voltage | 0~5 VDC |
Digital Output
Total Number of Outputs | 8 |
Output Logic | Sink |
Output Voltage | 11~28VDC |
Output Current | 0.5A per channel (Max 4A) |
Response Time | 300μs |
Current Consumption | 130mA@5VDC |
Mechanical
Enclosure Material | Plastic |
PCB Coating | Yes |
Dimensions WxHxD | 27 x 109 x 81 mm |
Mounting | 35mm DIN rail mounting |
Environmental
Storage Temperature | -20° ~ 70°C (-4° ~ 158°F) |
Operating Temperature | 0° ~ 55°C (32° ~ 131°F) |
Relative Humidity | 10% ~ 90% (non-condensing) |
Certification
IP Rating | IP20 |
EMC Immunity | Conforms to EN 55032: 2012+AC: 2013, Class A EN 61000-6-4: 2007+A1:2011 EN 55024: 2010+A1: 2015 EN 61000-6-2:2005 |
Customers who bought this product also bought:
Documents
Manuals
Certifications
- CE certification
- UL certification
- RoHS Certification
- Trade Agreement Act
- Conflict Minerals
- Russian Iron and Steel Declaration