How do I know what Ethernet/TCP port I should use when setting up my Maple Systems HMI?

Tags:

  • cMT
  • Networking

HMIs use a number of Ethernet/TCP ports when doing various tasks. Many of the features use Ethernet communication, often with a specified port. TN5127 has a list of the TCP ports used for various features:

cMT Series:

TCP PortUsage
21Default port for the FTP server, can be changed in System Parameter Settings within EasyBuilder Pro project
80, 443Default port for downloading an EasyBuilder Pro project file over ethernet, including over the open internet with the help of a VPN connection or Port Forwarding. Can be configured in the Download Menu under the Settings… menu
443Communication with EasyAccess 2.0 servers
502Default port for Modbus TCP/IP Communication
554Used for RTSP with IP Cameras
2000Ethernet Pass-through functionality, can be changed in System Parameter Settings within EasyBuilder Pro project
5800Used for WebView on the cMT-X series
5900Port for connecting to VNC server
8000Communication with Remote HMI, can be changed in System Parameter Settings within EasyBuilder Pro project
8001EasyDiagnoser communication
8002cMT Diagnoser communication
8005Used with EasyPrinter, can be changed in System Parameter Settings under Printer/Backup tab
8010Communication with Remote HMI, specifically between cMT series and HMI series devices. Can be changed in System Parameter settings under the Model tab
8080Used for Web Streaming on cMT-SVR models
9100Used with Common Unix Printing System (CUPS) for the cMT-3151
10275Search for HMI feature
10463cMT Diagnoser GUI
10763cMT GUI, cMT Viewer connection, and cMT Diagnoser connection. Affects User Access Control (UAC) and Trend/Event Display objects.

HMI Series

TCP PortUsage
21Default port for the FTP server, can be changed in System Parameter Settings within EasyBuilder Pro project
443Communication with EasyAccess 2.0 servers
502Default port for Modbus TCP/IP Communication
2000Ethernet Pass-through functionality, can be changed in System Parameter Settings within EasyBuilder Pro project
80, 5800VNC server (over HTTP and Java)
5900Port for connecting to VNC server
8000Communication with Remote HMI, can be changed in System Parameter Settings within EasyBuilder Pro project
8001EasyDiagnoser communication
8005Used with EasyPrinter, can be changed in System Parameter Settings under Printer/Backup tab
8010Communication with Remote HMI, specifically between cMT series and HMI series devices. Can be changed in System Parameter settings under the Model tab
8080Used for Web Streaming on the P and XL models of the HMI 5000 series
10275Search for HMI feature
20248Default port for downloading an EasyBuilder Pro project file over ethernet, including over the open internet with the help of a VPN connection or Port Forwarding. Can be configured in the Download Menu under the Settings… menu

See the related Controller Information Sheet for recommended TCP port numbers.