How do I reset the HMI’s memory?

Tags: FAQSoftware

How do I reset the HMI’s memory?

When using a Maple Systems HMI, the project, recipe (RW, RW_A, db), data log, and event log files are stored in permanent HMI (flash) memory. There are several ways to clear data in flash memory.

    1. Open Utility Manager, select the HMI series being configured in the upper-left corner, click [Publish] and then click [Download]. Select [Ethernet] or [USB cable]. Select all of the check boxes at the bottom of the dialog to reset memory locations in the HMI.
    1. Open project in EBPro, click [Download] and then select [Ethernet] or [USB cable]. Select all of the check boxes at the bottom of the dialog to reset memory locations in the HMI.
    1. Press the button on the lower-right corner of the HMI screen, select System Settings, enter default password 111111 or user-defined password. Go to [History] tab and check [Clear Recipe], [Clear Event log], and [Clear Data Log] check boxes and then click [Clear]. When finished, click [OK].
  1. Use the following system registers to clear data on HMI: LB-9023: delete all event log files on HMI memory when ON; LB-9026: delete all data sampling files on HMI memory when ON; LB-9028: reset all recipe data when ON.
Content Created by David Franzwa
Scroll to Top